XM31-915-HP
Power Supply
Alarms
Battery
Log In...
English
Español
Français
Português
Deutsch
Overview
Hardware
Power Supply
Batteries
Environmental I/O
Components
Network
Ethernet
Advanced
Interfaces
Network Services
Management
System Data
SNMP
Alarms
Utility Power
History
Power Supply Events
Power Supply Configuration
Battery Events
Standby Events
Alarm Log
d
Power Supply
Model
ALPHA/XM31-915-HP
Firmware
V2.06.0
Major Alarm
OK
Minor Alarm
OK
Operational Mode
Line
Charger Mode
Float
Tamper
Door closed
Power Supply Language
English
Power Supply Priority
Normal
d
Input
AC Line Mode
OK
Voltage
125.36
V
Current
3.36
A
Power
404
W
Frequency
60
Hz
Tap Status
Buck tap
Frequency Range
3.00
Hz
Current Limit
17.00
A
Input Power Consumption
327
Wh
1
Output
Voltage
86.99
V
Power
292
W
Apparent Power
332.30
VA
Frequency
60.02
Hz
Percent Load
25.40
%
Output Setting
90 V
Output Regulation
Fine
Over-current Tolerance
3.000
sec
Retry Delay
60
sec
Retry Limit
20
Active Drop Alarm
OK
Active Drop Threshold
50
W
Current
3.82
A
d
Inverter
Inverter Status
Off
End of Discharge Type
String
End of Discharge Level
1.75
V/cell
Reduced Peak Mode
Disable
Total Standby Events
112
Time Since Last Standby Event
0d 0h:00m
Time in Last Standby Event
0d 0h:00m
Total Time in Standby
130
min
Standby Events Since Reset
2
Time in Standby Since Reset
0
min
Time Since Reset
56
day(s)
Total Run Time
56
day(s)
Transformer Run Time
56
day(s)
Total Downtime
26d 13h:17m
Oil Cap Lifespan Consumed
1.1
%
d
Self Test
Deep Discharge Cycle
Timed
Test Countdown
5
day(s)
Test Duration
10
min
Test Interval
30
day(s)
Test Inhibit
No
→ CSV
→ Excel
Copyright © 2017-2023 EnerSys. All Rights Reserved.
www.alpha.com
|
www.enersys.com
Close